IAI America E-Con User Manual
Page 69
7
DEOHWRS5RERW77
61
I/O Parameters for TT Type
No. Parameter
name
Factory-set
value
Input range Set value
Remarks
1
Input/output port assignment
type
0 Read
only
0
0: Fixed assignment
2
Standard I/O1 fixed
assignment: Initial input port
number
000 Read
only
000
0 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
3
Standard I/O1 fixed
assignment: Initial output
port number
300 Read
only
300
300 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
4
Standard I/O2 fixed
assignment: Initial input port
number
32 Read
only
32
0 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
5
Standard I/O2 fixed
assignment: Initial output
port number
316 Read
only
316
300 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
6
Expansion I/O1 fixed
assignment: Initial input port
number
(Network I/F module)
48
-1 ~ 599
48
0 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
7
Expansion I/O1 fixed
assignment: Initial output
port number
(Network I/F module)
348
-1 ~ 599
348
300 + (multiple of 8) (The parameter is
invalid if a negative value is set.)
8
Reserved by system
-1
-1 ~ 599
-1
9
Reserved by system
-1
-1 ~ 599
-1
10
Standard I/O1 error monitor
0
0 ~ 5
0
0: Not
monitored
1: Monitored
2: Monitored (24-V I/O power errors
are not monitored)
3: Monitored. (Only 24-V I/O power
errors are monitored.)
* Some exceptions apply.
11
Standard I/O2 error monitor
0
0 ~ 5
0
0: Not
monitored
1: Monitored
2: Monitored (24-V I/O power errors
are not monitored)
3: Monitored. (Only 24-V I/O power
errors are monitored.)
* Some exceptions apply.
12
Expansion I/O1 error
monitor
(Network I/F module)
1
0 ~ 5
1
0: Not
monitored
1: Monitored
* Some exceptions apply.
13 Reserved by system
1
0 ~ 5
1
14
Network I/F card remote
input ports used
64
0 ~ 240
240
Multiple of 16
15
Network I/F card remote
output ports used
64
0 ~ 240
240
Multiple of 16