IAI America E-Con User Manual
Page 64
7
DEOHWRS5RERW77
56
4.2.2 ProfiBus-DP Communication Connector
The board-end connector is a D-sub 9-pin (female) connector recommended under the ProfiBus-DP standard
EN50170.
The network connector on the other end is not supplied.
Pin No.
Signal name
Explanation
1 NC
Not
connected
2 NC
Not
connected
3
B-Line
Communication line B (positive side)
4 NC
Not
connected
5
GND Signal
ground
6
+5V +5-V
output
7 NC
Not
connected
8
A-Line
Communication line A (negative side)
9 NC
Not
connected
Housing Shield
Cable
shield
* 1, 2, 4, 6, 7 and 9 are not used. (These signals need not be wired.)
4.2.3 Termination switch (Bus termination settings)
Among the units connected to a ProfiBus-DP network, the devices at both ends require termination to prevent
reflected waves from entering the bus line again.
This ProfiBus-DP module provides a termination switch that makes this termination easy.
The user need not install a separate terminal resistor. Never install an additional terminal resistor, as it may
have negative impact on bus communication or cause a communication error, etc.
.
Termination switch ON
Termination enabled
(If this switch is turned ON mistakenly when the module is connected in a position
other than the end of the network, bus communication may be negatively impacted
or a communication error, etc., may result.)
Termination switch OFF
Termination disabled
5.2.2
5.2.3