IAI America E-Con User Manual
Page 54
4. XSEL-R/S/RX/SX/RXD/SXD
46
(2) Example for when using PROFIBUS and I/O Board 1 together
It is how to establish the setting when using PROFIBUS to 256 points of each input and output from the top of
the extended I/O ports and assigning the I/O board (48 points for each input and output) to the standard I/O
ports.
Extended Input Ports No.1000 to 1255
Extended Output Ports No.4000 to 4255
(PROFIBUS board)
Standard Input Port No.0 to 47
Standard Output Port No.300 to 347
(I/O board)
xI/O Parameters
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
1
I/O Port Allocation Type
1
0 to 1
0
0:Fixed Allocation
1:Automatic Allocation
xReference 1 Priority of I/O Port Assignment when
automatically assigned
Port Number
(No.0 to 299/No.300 to 599)
1) Network I/F Module 1
2) I/O slot 1 (I/O1) Mounting board
3) I/O slot 2 (I/O2) Mounting board
* I/O slot 1 (I/O1) Assigned for the
continuously mounted range from
mounting board
xReference 2 Priority of extension I/O ports at
automatic assignment
Port Number
(No.1000 to 3999/No.4000 to 6999)
1) Network I/F Module 2
2) Expansion I/O unit
3) IA Net
2
Standard I/O Fix-Allocated
Input Port Start No.
0
-1 to 599
0
0+ (Multiples of 8)
[Ineffective when -1 is selected]
3
Standard I/O Fix-Allocated
Output Port Start No.
300
-1 to 599
300
300+ (Multiples of 8)
[Ineffective when -1 is selected]