IAI America E-Con User Manual
Page 22
3. X-SEL-J/K/P/Q/JX/KX/PX/QX
14
(2) ProfiBus-DP communication connector interface specifications
This is a 9-pin, female D-sub connector recommended by the ProfiBus-DP standard EN 50170.
Connector
Pin No.
Description
Contents
3 B-Line RxD
x TxD (Positive signal line)
5
GND
Shield
8
A-Line
/RxD
x /TxD (Negative signal line)
Housing
GND
Shield
* Pins 1, 2, 4, 6, 7 and 9 are not used (they need not be wired).
(3) Bus termination settings
Among the units connected to a ProfiBus-DP network, the devices at both ends require termination to prevent
reflected waves from entering the bus line again.
This ProfiBus-DP module provides a termination switch that makes this termination easy.
The user need not install a separate terminal resistor. Never install an additional terminal resistor, as it may
have negative impact on bus communication or cause a communication error, etc.
.
Termination switch ON
Termination enabled
(If this switch is turned ON mistakenly when the module is connected in a position
other than the end of the network, bus communication may be negatively impacted
or a communication error, etc., may result.)
Termination switch OFF
Termination disabled