3. X-SEL-J/K/P/Q/JX/KX/PX/QX

15

(4) Node address settings

The address of each ProfiBus-DP slave station is set using the “x10” and “x1” rotary switches shown in the figure
under (1).
Set a desired address according to the following rule:
Node address number = (“Value set by x10” rotary switch x 10) + (“Value set by x1” rotary switch x1)

Example)

Example of rotary switch settings

Target station number

“X10” setting (x 10)

“X1” setting (x 1)

9 0

9

12 1

2

Note 1) When setting ProfiBus-DP station numbers, remember that the ProfiBus-DP master station is always

assigned station number 0. Accordingly, numbers 1 to 99 are available for slave stations.

Note 2) The node address cannot be changed while the slave is communicating with the master.

(5) Monitor LED indications

LED Color Status

Definition

Description

(cause)

L1 -

Not used

Not defined

L2
Online

Green Steady light

Communicating
normally

x The module is operating normally (The module

is connected to the fieldbus and is therefore in
“online” state.)

L3
Offline

Red Steady

light

Offline

x The module is not connected to the fieldbus and

is therefore in “offline” state.

Unlit No

error

-

Blinking at 1 Hz I/O size error

x This LED blinks when the specified I/O size is

invalid.

Blinking at 2 Hz Connection not

yet established

x A system setting error (internal error)

L4
Error status

Red

Blinking at 4 Hz Communication

hardware error

x This LED blinks when a communication

hardware error has been detected during the
initialization of the system.