2. Specifications

2.1 Interface

Specifications

The table below lists the specifications of the ProfiBus-DP interface.

Item Specification

Remarks

Communication profile

ProfiBus-DP

Communication method

Hybrid method

Master/slave method with token passing

Number of connectable
stations

32 stations per segment

Up to 126 stations can be connected if a
repeater is used.

Communication data length

Maximum 244 bytes per frame

Physical profile

RS485

* A general physical profile is RS485.
* Use of a 9-pin D-sub connector is

recommended for IP20 configurations.

Baud rate (kbps)

9.6/19.2/93.75/187.5/500
1500/3000/6000/12000

*1

Maximum distance over the

entire network

Baud rate

Cable type

100 m

12,000/6,000/3,000 kbps

200 m

1,500 kbps

400 m

500 kbps

1000 m

187.5 kbps

Transmission distance

1200 m

9.6/19.2/93.75 kbps

Type A cable

Topology

Bus/tree/star

Cable

Single shielded twisted pair
cable

Type A cable

*1 The baud rate of a ProfiBus-DP network can be specified only when the ProfiBus-DP network is set up using

a configurator (*2).

The baud rate of all ProfiBus-DP slave modules is set with this configurator, and therefore a different baud rate
cannot be set for an individual slave station.

*2 For the ProfiBus-DP configurator, use the configurator recommended for the master unit.