4. XSEL-R/S/RX/SX/RXD/SXD

42

[3] PROFIBUS Board Use Setting

Set “1” (Monitoring: use PROFIBUS board) to I/O Parameter No. 235.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

235

Network I/F Module 2
Error Monitoring

1

0 to 5

ņ

0:No Monitoring (Not to monitor condition

of link to PLC (master))

1:Monitoring

[4] Node address setting

Set the node address to I/O Parameter No. 237

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

237

Network I/F Module 2
Node Address

0

0 to 125

ņ

PROFIBUS node address range: 0 to 125

Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.

[5] Number of I/O Port Setting

Set the number of ports to be used for I/O Parameters No. 231 to 232.
Note Set a number that is a multiple of 8.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

231

No. of Network I/F
Module 2 Remote
Input Ports

0

0 to 256

ņ

8 port unit

232

No. of Network I/F
Module 2 Remote
Output Ports

0

0 to 256

ņ

8 port unit