IAI America E-Con User Manual
Page 50
4. XSEL-R/S/RX/SX/RXD/SXD
42
[3] PROFIBUS Board Use Setting
Set “1” (Monitoring: use PROFIBUS board) to I/O Parameter No. 235.
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
235
Network I/F Module 2
Error Monitoring
1
0 to 5
ņ
0:No Monitoring (Not to monitor condition
of link to PLC (master))
1:Monitoring
[4] Node address setting
Set the node address to I/O Parameter No. 237
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
237
Network I/F Module 2
Node Address
0
0 to 125
ņ
PROFIBUS node address range: 0 to 125
Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.
[5] Number of I/O Port Setting
Set the number of ports to be used for I/O Parameters No. 231 to 232.
Note Set a number that is a multiple of 8.
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
231
No. of Network I/F
Module 2 Remote
Input Ports
0
0 to 256
ņ
8 port unit
232
No. of Network I/F
Module 2 Remote
Output Ports
0
0 to 256
ņ
8 port unit