3. X-SEL-J/K/P/Q/JX/KX/PX/QX

26

3.3.5 Setting Examples for P/PX/Q/QX Type Controllers

(1) Setting example when only a ProfiBus-DP board is used (automatic assignment)

Example: The following settings apply when the I/O ports of the ProfiBus-DP board are used by 32 input points

and 16 output points, each from the beginning, by leaving other I/O ports unused, just like when a
standard X-SEL I/O board (50-pin connector) is used.

[1] Enter “1” in I/O parameter No. 1 to specify automatic assignment. (Default setting)
[2] Set I/O parameter No. 10, “Standard I/O error monitor” to “2.” (Default setting)
[3] Set I/O parameter Nos. 14 and 15, “Input/output ports used,” and the settings are complete.

can be set in a range of 0 to 256 (but the value must be a multiple of 16)>.

Input port Nos. 000 to 015
Output port Nos. 300 to 315

Not used