3. X-SEL-J/K/P/Q/JX/KX/PX/QX
34
2)
Address assignment in the master station
When setting the configuration in 1) using a configurator, the numbers of inputs and outputs of the X-SEL set
for slave station 2 must be determined. (Here, it is assumed that the number of occupiable slave stations is
set to 16 words in the master station.)
3)
When the X-SEL conforming to the configuration example shown in 1) has total eight words of input and
output points (128 points), respectively.
The X-SEL’s I/O parameters are set as follows.
No.
Parameter name
Input range
Settings
Remarks
1
Input/output port assignment
type
0 ~ 20
1
0: Fixed assignment
1: Automatic assignment (Priority: Slot 1 ~)
* Ports are assigned automatically only for the
contiguous slots in use, starting from slot 1 =
For safety reasons.
2
Standard I/O fixed assignment:
Initial input port number (I/O1)
-1 ~ 599
000
0 + (multiple of 8) (The parameter is invalid if a
negative value is set.)
3
Standard I/O fixed assignment:
Initial output port number (I/O1)
-1 ~ 599
300
300 + (multiple of 8) (The parameter is invalid if
a negative value is set.)
4
Expansion I/O1 fixed
assignment: Initial input port
number (I/O2)
-1 ~ 599
-1
0 + (multiple of 8) (The parameter is invalid if a
negative value is set.)
(Slot next to standard I/O)
5
Expansion I/O1 fixed
assignment: Initial output port
number (I/O2)
-1 ~ 599
-1
300 + (multiple of 8) (The parameter is invalid if
a negative value is set.)
6
Expansion I/O2 fixed
assignment: Initial input port
number (I/O3)
-1 ~ 599
-1
0 + (multiple of 8) (The parameter is invalid if a
negative value is set.)
7
Expansion I/O2 fixed
assignment: Initial output port
number (I/O3)
-1 ~ 599
-1
300 + (multiple of 8) (The parameter is invalid if
a negative value is set.)
8
Expansion I/O3 fixed
assignment: Initial input port
number (I/O4)
-1 ~ 599
-1
0 + (multiple of 8) (The parameter is invalid if a
negative value is set.)
9
Expansion I/O3 fixed
assignment: Initial output port
number (I/O4)
-1 ~ 599
-1
300 + (multiple of 8) (The parameter is invalid if
a negative value is set.)
10 Standard I/O error monitor
0 ~ 5
2
0: Not monitored
11 Expansion I/O1 error monitor
0 ~ 5
0
1: Monitored
12
Expansion I/O2 error monitor
0 ~ 5
0
2: Monitored (only 24-V I/O power errors are
not monitored)
(Main application version 0.55 or later)
13
Expansion I/O3 error monitor
0 ~ 5
0
3: Monitored (only 24-V I/O power errors are
not monitored).
(Main application version 0.55 or later)
14
Network I/F card remote input
ports used
0 ~ 256
64
Multiple of 16
15
Network I/F card remote output
ports used
0 ~ 256
64
Multiple of 16