3. Installation and W
iring
(2)
Connecting the multiple axes
Item
Description
Maximum number of units that can
be connected
16 axes max. (depending on the operation mode)
Communication cable length
Total cable length: 100 m or less
SIO communication main line
Twisted-pair shielded cable (AWG22)
Recommended brand: Taiyo Electric Wire & Cable HK-SB/20276 x
L, 2P x AWG22
Terminal resistor
220
:, 1/4 W
Teaching pendant
PC, PLC
* The SIO communication main line must be prepared by the customer.
Each one unit of the junction, E-Con connector and terminal resistor are supplied with the controller link
cable.
Caution: [1]
If normal communication cannot be performed with a communication error occurring when the
total communication cable length is 10 m or more, connect the terminal resistor to the last
axis.
[2]
For the power supplies of the SIO converter and all controllers, make 0V in common.
[3]
Connect a shielded cable to FG on an axis basis.
[4]
If the total link cable length is more than 30 m, use the wire size of 22AWG or larger.
[5]
If the positive side of the 24-V power supply is grounded, do not connect the SIO converter
and the FG terminal of the PC to ground.
If the positive side of the 24-V power supply is grounded and no SIO converter is used, be
sure to use a SIO isolator (RCB-ISL-SIO). (Refer to the next page.)
Controller 1
E-Con connector (AMP 4-1473562-4: housing color green)
E-Con connector (AMP 3-1473562-4: housing color orange)
Junction (AMP 5-1473574-4)
Recommended: HK-SB/20276 x L, 2P x AWG22
SIO converter
SIO communication main line*
Terminal resistor
Controller link cable
Controller 2
Controller n