Problem

Description/Symptom

Probable Cause (Action to take)

Can’t Dispense

Flashing: 3, 2, or 1

RedJacket Functional Element – bad

False Leak Alarms

&

Leak Detected Light ON

(check / replace)

Multiple Nuisance

Vapor Recovery system malfunction

Alarms

(check / repair)

Check Valve leaking

(check / replace)

Air in lines

(dispense product after installation to remove

air from the lines)

Can’t Dispense

Flashing: 3

3 gph (or greater) GROSS Line Leak !...

&

Leak Detected Light ON

Test Failed

(see Chapter 4 about the Steps

to take When a Line Leak is detected)

Can’t Dispense

Flashing: 2

Monthly 0.2 gph Line Leak / Test Failed

&

Leak Detected Light ON

(see Chapter 4 about the Steps to take

When a Line Leak is detected)

Can’t Dispense

Flashing: 1

Annual 0.1 gph Manual Leak Test Failed

&

Leak Detected Light ON

(see Chapter 4 about the Steps to take

When a Line Leak is detected)

Flashing Alarm Error Codes are limited to a range of

80 to 85 ONLY !

Can’t Dispense

Flashing 80 Error Code

A manual 0.1 Annual leak test was

aborted by an attempted dispense.

(Push RESET to permit pumping when an

annual test was unintentionally started – or –

Do not hold the RESET TEST button down

longer than 4 seconds unless a manual test

is intended. Bag the dispenser / prevent

dispensing during the test and for 4 hours

before starting a Annual leak test ...also see

Chapter. 3)

Can’t Dispense

Flashing 81 Error Code

LSU internal component failure

(Push TEST-RESET to permit dispensing

once again. Schedule service at this site.)

Counting Days

Diagnostic Error Code 82

A 0.2 monthly leak test aborted because

Flashing (when viewed)

the line was not thermally stable

(A test will abort when the test result is

indeterminate after 18 cycles... neither a

pass or fail result can be determined. The

monthly test will start again after another

dispense. Call INCON when days count up

and when this Diagnostic Error Code is

consistently displayed.)