Note - 2 – Franklin Fueling Systems TS-LLD Installation Manual User Manual
Page 76

Problem
Description/Symptom
Probable Cause (Action to take)
Can’t Dispense
Flashing: 3, 2, or 1
RedJacket Functional Element – bad
False Leak Alarms
&
Leak Detected Light ON
(check / replace)
Multiple Nuisance
Vapor Recovery system malfunction
Alarms
(check / repair)
Check Valve leaking
(check / replace)
Air in lines
(dispense product after installation to remove
air from the lines)
Can’t Dispense
Flashing: 3
3 gph (or greater) GROSS Line Leak !...
&
Leak Detected Light ON
Test Failed
(see Chapter 4 about the Steps
to take When a Line Leak is detected)
Can’t Dispense
Flashing: 2
Monthly 0.2 gph Line Leak / Test Failed
&
Leak Detected Light ON
(see Chapter 4 about the Steps to take
When a Line Leak is detected)
Can’t Dispense
Flashing: 1
Annual 0.1 gph Manual Leak Test Failed
&
Leak Detected Light ON
(see Chapter 4 about the Steps to take
When a Line Leak is detected)
Flashing Alarm Error Codes are limited to a range of
80 to 85 ONLY !
Can’t Dispense
Flashing 80 Error Code
A manual 0.1 Annual leak test was
aborted by an attempted dispense.
(Push RESET to permit pumping when an
annual test was unintentionally started – or –
Do not hold the RESET TEST button down
longer than 4 seconds unless a manual test
is intended. Bag the dispenser / prevent
dispensing during the test and for 4 hours
before starting a Annual leak test ...also see
Chapter. 3)
Can’t Dispense
Flashing 81 Error Code
LSU internal component failure
(Push TEST-RESET to permit dispensing
once again. Schedule service at this site.)
Counting Days
Diagnostic Error Code 82
A 0.2 monthly leak test aborted because
Flashing (when viewed)
the line was not thermally stable
(A test will abort when the test result is
indeterminate after 18 cycles... neither a
pass or fail result can be determined. The
monthly test will start again after another
dispense. Call INCON when days count up
and when this Diagnostic Error Code is
consistently displayed.)
NOTE
☞