Control Unit Installation

Page 2.3 - 1

2.3

2.3

TS-LLD CU Installation & Wiring

Control Unit ( CU ) Installation Steps

Follow the installation steps (below) and in the order that they appear:

DANGER

Electrical Shock Hazard. BEFORE installing, servicing or

working on this equipment,

turn off all submersible pump power (240 VAC) and

pump relay coil / dispenser power at the electrical panel.

Tag, secure / lockout

these circuit breakers in the off position to prevent accidental or unauthorized
circuit breaker closure.

Failure to turn off power will result in severe injury or

death ! Check all wiring terminals for the absence of power before proceeding.

Note: Circuit breaker contact(s) can stick closed even when the circuit breaker

lever is in the off position.

You must know the dispense line number, product dispensed, and which pump

relay box (motor control box) is associated with this line.

1) Select an accessible mounting location for the control unit (see Figures 2.3-1 &

2.3-3), and remove the appropriate conduit knockouts. The CU is usually

mounted above the pump relay box (shown here)... other locations are possible.

Figure 2.3-1 CU Internal & Bottom Views, and Relay Box Top View

1 4 8 5 A

2 4 8 5 B

3 D S Y 1

4 D S Y 2

5 A L A R M

1 1 1 0 V

2 N E U

3 P -O U T

TB1

4 P -IN

F1

U P

S IG R TN

TB2

IN T E R N A L V IE W

C U E N C L O S U R E

B O T T O M V IE W

R E M O V E

K N O C K O U T

F O R 1 /2 IN C H

E L E C T R IC A L

F IT T IN G

A T B O T T O M

K N O C K O U T S F O R E L E C T R IC A L F IT T IN G S

T O P V IE W S H O W N

Contents:

Control Unit Installation Steps (Location, Product Configuration,
TS-2000 Configuration, Mounting the Control Unit, Relay Box &
Control Unit Wiring TABLE 2.3-1)

Wiring Diagrams & Schematics (Pump Control Relay Box,
Single Phase 240 VAC, 3 Phase 240 VAC, 3 Phase RedJacket BigFlo,
3 Phase 240 VAC - FE Petro - STP & IST applications)

Final Installation Steps

NOTE