Overview and theory of operation - 1, Figure 1.1, Lsu outline - 1 – Franklin Fueling Systems TS-LLD Installation Manual User Manual
Page 11: Figure 1.2, Cu outline dimensions - 1, Overview and theory of operation

1
TS-LLD Electronic
Line Leak Detector system –
Overview
Overview and Theory of Operation
The
INCON TS-LLD is an electronic line leak detector
system. It has two components: a Control Unit (or CU)
and a Leak Sensing Unit (or LSU). The CU is mounted in
the station near the pump control relay box, and the LSU is
installed in the line leak detector port at the submersible
pump housing. One system per pump is required to detect
leaks from a pressurized fuel line.
The TS-LLD detects leaks in the pipeline leading from the
submersible pump to the dispenser. To comply with
current EPA regulations, three types tests are provided.
These are: a 0.1 gph annual test, a 0.2 gph monthly test,
and a 3.0 gph hourly test, which run at full line pressure.
8 IN C H
L E A D S
M I C A B L E
A D A P T E R
- J U N C T IO N
B O X S ID E
2 3 .5 IN C H E S
A P P R O X .
O V E R A L L
L E N G T H
A S S E M B L E D
2 IN C H N P T
- L IN E L E A K
P O R T S ID E
M I C A B L E
Figure 1.2 CU Outline Dimensions
3.35
TS
-L
LD
C
U
S
eri
al
N
um
be
r
x
x
x
x
x
x
x
x
F R O N T V IE W
R IG H T S ID E V IE W
xxxxxxxx
Line #:
P roduct:
4.35
2.25
0.60
K n o c k o u t f o r
1 /2 in c h f it t in g
- Ty p ic a l -
Note: A ll Dimens ions are in inc hes , and are approx imate
TO P & B O TTO M V IE W - C O N TR O L U N IT (C U )
Contents:
•
Overview and theory of
Operation
•
Leak Test Requirements
and Length
•
The LSU (Leak Sensing Unit)
•
Communications
•
The CU (Control Unit)
•
Operator Interface