Overview

Page 1 - 1

1

1

TS-LLD Electronic

Line Leak Detector system –

Overview

Overview and Theory of Operation

The

INCON TS-LLD is an electronic line leak detector

system. It has two components: a Control Unit (or CU)
and a Leak Sensing Unit (or LSU). The CU is mounted in

the station near the pump control relay box, and the LSU is

installed in the line leak detector port at the submersible
pump housing. One system per pump is required to detect

leaks from a pressurized fuel line.

The TS-LLD detects leaks in the pipeline leading from the

submersible pump to the dispenser. To comply with

current EPA regulations, three types tests are provided.
These are: a 0.1 gph annual test, a 0.2 gph monthly test,

and a 3.0 gph hourly test, which run at full line pressure.

8 IN C H

L E A D S

M I C A B L E

A D A P T E R

- J U N C T IO N

B O X S ID E

2 3 .5 IN C H E S

A P P R O X .

O V E R A L L

L E N G T H

A S S E M B L E D

2 IN C H N P T

- L IN E L E A K

P O R T S ID E

M I C A B L E

Figure 1.1 LSU Outline

Figure 1.2 CU Outline Dimensions

3.35

TS

-L

LD

C

U

S

eri

al

N

um

be

r

x

x

x

x

x

x

x

x

F R O N T V IE W

R IG H T S ID E V IE W

xxxxxxxx

Line #:

P roduct:

4.35

2.25

0.60

K n o c k o u t f o r

1 /2 in c h f it t in g

- Ty p ic a l -

Note: A ll Dimens ions are in inc hes , and are approx imate

TO P & B O TTO M V IE W - C O N TR O L U N IT (C U )

Contents:

Overview and theory of
Operation

Leak Test Requirements
and Length

The LSU (Leak Sensing Unit)

Communications

The CU (Control Unit)

Operator Interface