Line leak test light - 4, Line leak detected light - 4, Reset test touch button — press to: - 4 – Franklin Fueling Systems TS-LLD Installation Manual User Manual
Page 60: Note - 4, Display diagnostic test codes: - 4, Starting a 0.1 gph annual precision leak test - 4, Requirements: - 4, Definition: quiet-time - 4

CU Component Location & Function
(Continued... )
Line Leak Test light
➁
Turns on when any line leak test starts and stays on during the entire test. The light
only turns off when:
1) a test finishes
2) a dispense occurs
3) the Reset Test button is pushed
Line Leak Detected light
➂
Flashes on and off continuously when a line leak test fails. This light will continue to
flash until another test – of equal or greater precision – finally passes.
Display Functions, Codes & Concise Instructions
➃
RESET TEST touch button
➄
...
press to:
•
Abort, Stop, or Cancel any line leak test (the Line Leak Test light
➁
will also
turn off when the RESET TEST is pushed)
•
Clear any flashing Error codes and Enable product dispensing (except the
Flashing 83 or 84 Error codes)... error codes will reappear if the problem remains
•
Reset and restart automatic line leak testing (the leak detected light
➂
cannot
be reset if a leak was detected)...
Automatic Line Leak Tests resume after product
is dispensed.
•
Perform a Self-Test (one push displays an
88
) see Chapter - Section 6.1
•
Display diagnostic codes (see Chapter - Section 6.1)
•
Start a manual, 0.1 gph annual precision line leak test
Display Diagnostic Test Codes:
See Chapter - Section 6.1 for directions about Diagnostic Display Test Codes
Starting a Manual 0.1 gph Precision Leak Test
Requirements:
Prevent dispensing / bag dispenser during this time. The manual test needs 4
hours of
quiet-time
BEFORE it is started, and takes about 13 minutes to finish.
Definition:
quiet-time
is the inactive period –
between– product dispensing