1 test fail alarms, warnings & error codes - 1, Display codes - 1, Alarms and error codes – Franklin Fueling Systems TS-LLD Installation Manual User Manual
Page 73: Section 6.1, 1 test fail alarms, warnings & error codes

6.1
Test Fail Alarms, Warnings &
Error Codes
Display Codes
The following Normal, Alarms, Warnings, and Error Codes are displayed at the
control unit at this publication date.
Normal Display Codes (on steady – not flashing)
DISPLAY CODE
DESCRIPTION
00 to 28
Number of Days since a 0.2 gph monthly-compliance leak test
passed (00 = zero days, 09 = nine days). The display counts up
(advances a day) for every 24 hours that the test has not finished
with a passed result.
88
System OK... the control unit electronics and all segments of the
2 digit display are working correctly.
Flashing Display Codes (Alarms, Warnings, and Error Codes)
Flashing Error Codes can occur in range from 80 to 85 only !
DISPLAY CODE
DESCRIPTION
1
Alarm 0.1 gph Annual (manual) Leak Test Failed
2
Alarm 0.2 gph Monthly-Compliance leak test Failed
3
Alarm 3 gph Hourly – gross – leak test Failed
29 – 32
Warning ! the line is almost out of compliance ! It has been
nn days (represented by the flashing number) since the last 0.2
gph Monthly-Compliance test passed.
Also see 84 Error Code.
80
Error Manually started, 0.1 gph Annual precision leak test was
aborted... a dispense was attempted while the test was running
81
Error A component failed within the Leak Sensing Unit
82
Error Indeterminate 0.2 gph leak test result — the line was not
thermally stable. This error will not disable dispensing and can be
viewed when RESET-TEST is pushed 4 times.