1 test fail alarms, warnings & error codes - 1, Display codes - 1, Alarms and error codes – Franklin Fueling Systems TS-LLD Installation Manual User Manual

Page 73: Section 6.1, 1 test fail alarms, warnings & error codes

background image

Test Fail Alarm & Error Codes

Page 6.1 - 1

6.1

6.1

Test Fail Alarms, Warnings &

Error Codes

Display Codes

The following Normal, Alarms, Warnings, and Error Codes are displayed at the

control unit at this publication date.

Normal Display Codes (on steady – not flashing)

DISPLAY CODE

DESCRIPTION

00 to 28

Number of Days since a 0.2 gph monthly-compliance leak test

passed (00 = zero days, 09 = nine days). The display counts up

(advances a day) for every 24 hours that the test has not finished

with a passed result.

88

System OK... the control unit electronics and all segments of the

2 digit display are working correctly.

Flashing Display Codes (Alarms, Warnings, and Error Codes)

Flashing Error Codes can occur in range from 80 to 85 only !

DISPLAY CODE

DESCRIPTION

1

Alarm 0.1 gph Annual (manual) Leak Test Failed

2

Alarm 0.2 gph Monthly-Compliance leak test Failed

3

Alarm 3 gph Hourly – gross – leak test Failed

29 – 32

Warning ! the line is almost out of compliance ! It has been

nn days (represented by the flashing number) since the last 0.2

gph Monthly-Compliance test passed.

Also see 84 Error Code.

80

Error Manually started, 0.1 gph Annual precision leak test was

aborted... a dispense was attempted while the test was running

81

Error A component failed within the Leak Sensing Unit

82

Error Indeterminate 0.2 gph leak test result — the line was not

thermally stable. This error will not disable dispensing and can be

viewed when RESET-TEST is pushed 4 times.

Contents:

Normal Display Codes (on steady – not flashing)

Flashing Alarm, Warning, and Error Display Codes

Diagnostic Display Codes