Page 44: Figures 2.3 - 9 & 10, Page 2.3 - 10 ts-lld installation guide

background image

2.3

Page 2.3 - 10

TS-LLD INSTALLATION GUIDE

Figure 2.3-9 Three Phase 240 VAC Supply – Starter – Motor Control Box – and BigFlo Pump

(3 wire)

Interface Schematic to TS-LLD

Reference Site Layout

Figure 2.2 - 15

INCON TS-LLD & RedJacket Big Flo Three Phase Wiring

Diagram

for newer 3 wire Three Phase motors

1) If the motor starter coil is 230 VAC then do not wire to neutral -- wire to M1. 2) Observe color code L1 L2 L3 phase sequence for proper rotation of motor. 3) All conduit fittings, EYS seal fittings, and junction boxes in manholes or other Hazardous areas are to be explosionproof rated for: Class 1, Div 1, Group D and wet locations

DANGER ELECTRICAL SHOCK HAZARDS. TURN OFF AND LOCK-OUT THE SUBMERSIBLE PUMP POWER SOURCE (L1, L2, L3 - AT THE CIRCUIT BREAKER) - BEFORE - WORKING ON THIS EQUIPMENT. FAILURE TO TURN OFF THE THREE PHASE POWER SOURCE WILL RESULT IN SEVERE INJURY OR DEATH.

Three Phase Motor Starter (ref. Note 1)

N (N o t e 1)

Dispense Switch

Separate wires must be run.

ORG

RED

Three Phase BigFlo

STP...newer 3 wire version...

Overloads (OLs) in series w/ T1 & T3

BLK

T2

T1

T3

TS-LLD LSU (Leak Sensing Unit) at diaphragm valve

BLK

Aux. Control Relay Box (remove dashed wires)

L2

L1

L3

Electrical Power Panel

L2

L1

GND

L3

N

M2

S2

S1

M1

L1

N

L2

Install Line Filter

Cap (between L1 and L2)

P/N

020-0028

2 NEU

NOTES

Neutral (WHT)

GND

S2 (BRN) Pump On Sig. (L1 is source)

RLY COIL (RED)

N

TB1

3 P-OUT

SIG RTN

4 P-IN

TS-LLD Control Unit (CU)

Power Source = L1

No connection. Run wire through the donut-shaped Pickup Coil

L1 Line (BLK)

Pickup Coil

M1 (ORG)

RLY N.O. (ORG)

TB2

1 485A

1 110V

F1

5 ALARM

4 DSY2

2 485B 3 DSY1

GND

N