Flashing Error Codes (continued... )
Flashing Error Codes can occur in range from 80 to 85 only !
DISPLAY CODE
DESCRIPTION
83
Error Leak Sensing Unit is not communicating with the Control
Unit
84
Error The line is Out of Compliance (it has been at least 33 days
since the last 0.2 gph Monthly-Compliance test has passed.
85
Error Leak Sensing Unit requires service
Diagnostic Display Codes
These are obtained by repeatedly pressing the RESET button...
DO NOT hold the TEST button
down longer than 4 seconds, otherwise a manual leak test will start.
First press:
88
System OK... all 7 segments of the 2 digit display are on and are
working correctly when 88 is displayed (
88 is solid/not flashing).
Second press:
XX
Solid or flashing number which represents the
average tempera-
ture differential
of the last 0.2 gph leak test. Record this number
for assistance from INCON.
Third press:
XX
Solid or flashing number for the
accumulated power reading
of
the last 0.2 gph leak test (00 - 99 solid ...solid 99 represents a
number from 99 to 149 and flashing 99 represents a number from
150 and above). Record this number for assistance from INCON.
Fourth press:
XX
Flashing number which represents the
last flashing Leak
Detected Alarm code or Error code
. Record this number for
assistance from INCON.