TS-LLD INSTALLATION GUIDE

Flashing Error Codes (continued... )

Flashing Error Codes can occur in range from 80 to 85 only !

DISPLAY CODE

DESCRIPTION

83

Error Leak Sensing Unit is not communicating with the Control

Unit

84

Error The line is Out of Compliance (it has been at least 33 days

since the last 0.2 gph Monthly-Compliance test has passed.

85

Error Leak Sensing Unit requires service

Diagnostic Display Codes

These are obtained by repeatedly pressing the RESET button...

DO NOT hold the TEST button

down longer than 4 seconds, otherwise a manual leak test will start.

First press:

88

System OK... all 7 segments of the 2 digit display are on and are

working correctly when 88 is displayed (

88 is solid/not flashing).

Second press:

XX

Solid or flashing number which represents the

average tempera-

ture differential

of the last 0.2 gph leak test. Record this number

for assistance from INCON.

Third press:

XX

Solid or flashing number for the

accumulated power reading

of

the last 0.2 gph leak test (00 - 99 solid ...solid 99 represents a

number from 99 to 149 and flashing 99 represents a number from

150 and above). Record this number for assistance from INCON.

Fourth press:

XX

Flashing number which represents the

last flashing Leak

Detected Alarm code or Error code

. Record this number for

assistance from INCON.