Troubleshooting Guide

Page 6.2 - 1

6.2

6.2

TS-LLD Troubleshooting Guide

Display Codes

This chapter contains a current listing of Warnings, Alarms, and Error Codes that
may be displayed at the control unit. Before attempting any service, maintenance

or troubleshooting work on this system, be sure to review and follow all

instructions, and heed all cautions and warnings in this manual... see Chapter 5.
Also, review all appropriate manufacturers’ documentation, and applicable codes.

WARNING

Disconnect power sources before troubleshooting and before

removing any enclosure cover. Failure to turn power off will create an electrical

shock hazard which may cause injury or death !

Abbreviations used in this Chapter:

STP =

Submerged Turbine Pumps / Submersible Pumps

LSU =

Leak Sensing Unit

CU =

Control Unit

Problem

Description/Symptom

Probable Cause (Action to take)

No Display

No LED lights on

Power is off

Can’t Dispense

(Check STP Circuit Breakers... are they on ?)

CU fuse F1 is open/blown (See Chapter 5

about replacing F1)

CU box was wired incorrectly. See

Chapter 2.3).

Can’t Dispense

Flashing 29, 30, 31 or 32

Monthly-Compliance Warning !

(Push RESET TEST to permit pumping for

another day (up to 24 hours)...see Chapter

3.)

Days may keep counting up in busy stations

where there isn’t enough

quiet-time

be-

tween dispensing to finish a monthly test.

(Are the turbines turned off after hours ?)

(Ask the station to keep the circuit breakers /

turbine(s) on so the monthly tests can finish

after hours.)

Contents:

Problem

Description / Symptoms

Probable Cause (and Action to Take)