2.2

Page 2.2 - 8

TS-LLD INSTALLATION GUIDE

9)

Stuff the wires back into the pump housing and carefully finish bending the MI

cable so that the cable adapter engages the threaded opening of the junction box.

Make sure to push the wires down enough to avoid pinching, or cutting through

the wire insulation from the cable adapter when it is tightened down.

Reference

Figure 2.2-9, or 2.2-10.

10)

Tighten the MI cable adapter (new junction box cover) after making sure that

compression fitting is loose and is able to rotate freely — to prevent bending

and twisting damage to the MI Cable. Apply electrically conductive pipe dope to

the cover or the junction box. Use a 12 inch adjustable wrench. Reference

Figure

2.2-9, or 2.2-10.

Figure 2.2-9 MI Cable Adapter Installation – RedJacket

®

Pump Housing

M I CABLE

STATION

CONDUIT

P IP E L IN E

PUMP

HOUSING

LINE LEAK

DETECTOR