LSU Installation

Page 2.2 - 7

2.2

Figure 2.2-8 Line Leak Detector Wiring – FE Petro Pump Housing

DANGER

Make sure you check these wires for the absence of power

before proceeding. All pump power (240 VAC) and pump relay / dispenser power

must be off before this installation is started, otherwise a lethal hazard will be
created which could kill you or others.

Note: A circuit breaker contact(s) can

stick closed even when the circuit breaker is in the off position.

8)

Leak Sensing Unit Wiring – Reference Figure 2.2-7, or 2.2-8.

a) Use one of the supplied red wire nuts, and twist one wire lead from pump

together with one of the black wire leads from the LSU.

b) Again use a red wire nut, and twist the remaining lead from pump together

with the remaining black wire lead from the LSU.

c)

For Canadian TS-LLD leak sensing units only:

connect the green (ground)

wire from the pump to the green LSU wire.

PUMP

HOUSING

STATION

CONDUIT

PORT

M I CABLE

ADAPTER

M I CABLE

PIPELINE

LINE LEAK

DETECTOR