beautypg.com

Ts-2000 tank gauge interface - 3, Note - 3, Ts-2000 tank gauge interface – Franklin Fueling Systems TS-LLD Installation Manual User Manual

Page 51

background image

TS-LLD – Tank Sentinel ATG Console Interface

Page 2.4 - 3

2.4

BLK

RED

UP

F1

TB1

1 485A

2 485B

3 DSY1

4 DSY2

5 ALARM

3 P-OUT
4 P-IN

2 NEU

1 110V

TB2

SIG RTN

7

6

4

3

1

5

INPUT 4

{ spare 2 }

INPUT 2

{ leaktest }

{ spare 1 }

INPUT 3

{ setup }

INPUT 1

8

2

J5

PC BOARD

GAS

J2

DIESEL

J1

Alternate

Jumper

Link Position:

DIESEL

GAS

DIESEL

J2

for Gasoline

for Diesel, or

Fuel Oils

Alternate

Jumper

Link Position:

GAS

J2

Green Connector (J1)

for Gasoline

J2

GAS

REPOSITION

JUMPER

LINKS

ENCLOSURE

COVER (SHIELD ON)

COVER (SHIELD OFF)

TB1-

SIG RTN

TB2-5

Use:

INPUT 1 for Line 1

INPUT 2 for Line 2

INPUT 3 for Line 3

INPUT 4 for Line 4

Discrete

Input Signal

(GND)

J5-Even

Numbered

Terminals

J5-Odd

Numbered

Terminals

DC Input

INCON TS-LLD Line Leak Detector

- Control Unit

2 Pulses = Passed 0.2 GPH Test

3 Pulses = Failed 0.2 GPH Test

Activated = Failed 3.0 GPH Test

for

TS-2000 Interface

for

TS-2000 Interface

Standard TGI

(TS-1000) Interface

INCON TS-2000 AUTOMATIC TANK GAUGE:

Discrete Input Interface terminals

for the TS-LLD Line Leak Detector

One Pulse = + 5 vdc

On 1 second and Off 1 second

DIESEL

Factory Default

Jumper

Link Positions:

Plastic shield is mounted

over the PC board

Remove the shield to set the

jumper link to the correct

position as shown below

(replace the shield before

reinstalling the cover).

TS-2000 Tank Gauge Interface

Remove the TS-LLD control unit cover & plastic shield, and reposition the blue

jumper links as shown in the diagram below. Do this when wiring to the discrete
input terminals of an

INCON model TS-2000 ATG.

TS-LLD Alarm Output ratings (from TB2-5) are:

+ 5 VDC, 60 milliAmps max. (resistive loads)

— the output is from an Open

Collector transistor with a 270 ohm resistor tied to an internal + 5 V DC supply.

Figure 2.4-3 TS-2000 – TS-LLD Line Leak Detector Interface

NOTE