Installation Guide for Galaxy Power Systems
15 - 18 Power Up and Installation Completion
Issue 12 August 2012
Setting the Low-Voltage Load Disconnect Feature, continued
Setting the LVLD Feature, continued
Step
Action
2
The default thresholds are:
• Galaxy Millennium Controller:
disconnect voltage:
+22V (for +24V systems) or -44V (for -48V systems)
reconnect voltage:
+24V (for +24V systems) or -48V (for -48V systems)
• Galaxy Vector Controller:
disconnect voltage:
+21V (for +24V systems) or -43.20V (for -48V systems)
reconnect voltage:
+22.20V (for +24V systems) or -44.40V (for -48V systems)
To set the thresholds to other values, enter the appropriate key
sequence:
• Galaxy Millennium Controller:
Main
Config LVD (Basic) or Low V Disc (Intelligent)
Contactor 2 Type-Load Change Thresholds
Enter
• Galaxy Vector Controller:
Main
Configuration Contactors Contactor 2
Disconnect/Reconnect
Save
Note: The factory default for all load disconnect contactors in the
system is hardwired as Contactor 2. In a Millennium system this
can be changed to Contactor 3 to allow some load contactors to
open at different thresholds. To change, move the jumpers on the
associated EBV contactor drive boards as shown in Figure 8-13.
Then set Millennium’s Contactor 3 configuration to Load with the
desired thresholds as described above.