Current limiting resistors, Mounting locations, Figure 10-1: possible rpm mounting locations – GE Industrial Solutions Galaxy Power Systems User Manual
Page 144: Overview, continued

Installation Guide for Galaxy Power Systems
10 - 2 Remote Peripheral Monitoring
Issue 12 August 2012
Overview, continued
Current Limiting
Resistors
Current limiting resistors (100K-ohm) are required for the measurement
inputs of the voltage, current, and binary modules. Comcode 847540424
current limiting resistor assemblies are available for connections that do
not already have them. All shunts (load and battery) and some voltage
points that are provided with the GPS cabinet already have current
limiting resistors; check T-83314-30 for resistor presence.
For the 214A Control Relay module, the maximum relay contact voltage
is 110Vdc and maximum current is 0.3Adc. Wiring depends on the
voltage, current, local building codes, and various other characteristics
of the controlled point.
Mounting
Locations
Figure 10-1 shows possible mounting locations for the RPMs.
Figure 10-1: Possible RPM Mounting Locations
Part of Module Kit
Modules can also be mounted on blank 6", 9", and 12"
panels inside the cabinet (H569-434/H569-436/H569-437
G90, G91, and G92).
Panel
848535332
Panel
848412367
(Provided with H569-434 G28 and G29
1200A and 4800A Distribution Only Cabinets)
6-32 Nut
901233502
10-32x7/16" Screw
901252726
10-32x7/16" Screw
901252726