14.6.2 Hoisting and lowering prevented

Check the input status from parameter 1-2-14

HIN

LIN

FIN

MFI1

MFI2

1

0

1

0

0

If the unit does not receive any input commands, check the control voltage and the commanding
inputs

Check the terminal

It is normal that a Voltmeter shows a disturbance value. The measured voltage may appear to be
more than twice the rated control voltage, on “non-active” inputs. This voltage has however no
power, and can not activate the input.

Check the output status from parameter 1-2-15

HOUT

LOUT

FOUT

RS

ROUT

1

0

1

1

1

If the outputs are to be active, but the controlled device not, check the terminals, wiring and
controlled device. Usually the fault “Run_FB” appears on the display.