14.1.10

Fault Supply vol

F_SPh

Main supply fault, one phase missing

Check that the main voltage connects simultaneous to the control voltage

Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)

In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO

14.1.11

Fault Phaseorder

F_Sor

Main supply fault, incorrect phase order (supervision is carried out only once after each power-
ON)

Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)

Check the phase-order

Check the phase order of the wires through the current transformers

Check the connections of the current transformer

In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO

14.1.12

Fault CParameter F_CP

Internal parameter read or write fault

Incorrect check sum in reading the memory or internal hardware fault in the unit

14.1.13

Fault MParameter F_MP

Internal parameter read or write fault

Incorrect check sum in reading the memory or internal hardware fault in the unit