14.1.10
Fault Supply vol
F_SPh
Main supply fault, one phase missing
•
Check that the main voltage connects simultaneous to the control voltage
•
Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)
In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO
14.1.11
Fault Phaseorder
F_Sor
Main supply fault, incorrect phase order (supervision is carried out only once after each power-
ON)
•
Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)
•
Check the phase-order
•
Check the phase order of the wires through the current transformers
•
Check the connections of the current transformer
In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO
14.1.12
Fault CParameter F_CP
Internal parameter read or write fault
•
Incorrect check sum in reading the memory or internal hardware fault in the unit
14.1.13
Fault MParameter F_MP
Internal parameter read or write fault
•
Incorrect check sum in reading the memory or internal hardware fault in the unit