1 hoist motor overheating supervision instructions – R&M Materials Handling HOIST MONITORS User Manual
Page 25

R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319
25/105
R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.
5.3.1 Hoist motor overheating supervision instructions
Param. Name
Description
4-4
T1
Temperature measurement channel 1 parameters
Selects the function of temperature measurement channel 1:
NU
Not used
Motor without thermistors or only one sensor that is connected to the
temperature input 2.
PTC
Motor thermistor or
Bimetal thermal switch
Two speed motors typically only have one set of thermistors, for both low speed
and high speed windings.
Bwear
Brake wear sensor
See section Hoist Brake- Wear supervision
A NTC
Type A NTC sensor
B NTC
Type B NTC sensor
4-4-1
T1 operat.
C NTC
Type C NTC sensor
Determines the type of thermistors in the low speed windings, connected to the
temperature input 1
Manufacturer’s hoisting motors used in motor-torque calculation overload
systems are as a standard equipped with type B NTC thermistors
Param. Name
Description
4-5
T2
Temperature measurement channel 2 parameters
Selects the function of temperature measurement channel 2:
NU
Not used
Motor without thermistors or only one sensor that is connected to the
temperature input 1.
PTC
Motor thermistor or
Bimetal thermal switch
Two speed motors typically only have one set of thermistors, for both low speed
and high speed windings.
Bwear
Brake wear sensor
See section Hoist Brake- Wear supervision
A NTC
Type A NTC sensor
B NTC
Type B NTC sensor
4-5-1
T2 operat.
C NTC
Type C NTC sensor
Determines the type of thermistors in the low speed windings, connected to the
temperature input 1
Manufacturer’s hoisting motors used in motor-torque calculation overload
systems are as a standard equipped with type B NTC thermistors
Param.
Value
Description
Note
4-10
Single sup
Accessible with password 4: 8124
4-10-1
OT run ?
No / Down
Hoisting and lowering is prevented when the
overtemperature supervision trips.
If, for safety reasons, local legislation or customer demands,
lowering the load is required when the temperature supervision
has tripped, set this parameter to: “Down”
4-10-2
OT limit
150C
Sets the tripping level of the overtemperature
supervision in degrees Celsius, steps of one
degree. Only with NTC-thermistor.
Consult with the motor data sheets for the maximum allowed
temperature for the motor. Default for manufacturer’s squirrel
cage motors: 150°C