beautypg.com

Identifying multi-wire branch circuits, Identifying characteristic, Figure f-4 multi-wire branch circuit wiring – Xantrex Technology SW Plus 4024 User Manual

Page 320: Figure f-4, Warning: shock hazard

background image

Multi-wire Branch Circuit Wiring

F–4

976-0043-01-02

Identifying Multi-wire Branch Circuits

Identifying
characteristic

Multi-wire branch circuits can be identified by removing the cover on the
load center and inspecting the wiring. Conventional 120 Vac circuits are
identified by a 2-wire-plus-ground (black, white, and copper) “romex” for
each circuit. Multi-wire branch circuits use a 3-wire-plus-ground
arrangement (black, red, white and copper) for each circuit run.

If this arrangement exists in the panel and it is being powered by a stand-
alone 120 Vac inverter, a potential fire hazard exists! For safety, these
circuits must be rewired to meet code.

WARNING: Shock Hazard

The next step involves opening the load center, exposing live circuits. This
procedure should only be performed by qualified persons or electricians.

Figure F-4 Multi-wire Branch Circuit Wiring

Ground Bare

Copper

Single Neutral

White

Red From L2

Breaker

Red From L1

Breaker

To Branch Circuits

This manual is related to the following products: