Table 7-2, Advanced setup default settings for the – Xantrex Technology SW Plus 4024 User Manual
Page 183
![background image](/manuals/229206/183/background.png)
Advanced Setup Summary
976-0043-01-02
7–5
Table 7-2 Advanced Setup Default Settings for the
Sine Wave Plus
4024 and 4048 Models
Advanced Setup Menus
Sine Wave Plus
4024
Sine Wave Plus
4048
See Page
Range/Display
Default
Settings
Range/Display
Default
Settings
20 Silent Setup Menu
“20 Silent Setup Menu” on page 7–13
for details.
20A Refloat High Volts DC
16.1 to 33.9
28.4
32.2 to 67.8
56.8
20B Refloat Low Volts DC
16.1 to 33.8
25.0
32.2 to 67.8
50.0
20C Float Done Amps AC
00 to 40
10
00 to 40
10
20D Must Float Time Min
00 to 255
05
00 to 255
05
End Menu 20
21 Grid AC1 Usage Menu
“21 Grid (AC1) Usage Menu” on page 7–16
for details.
21A Grid Usage
SB BX
SB
SB BX
SB
21B Grid Usage Begin h:m
00:00 to 23:50
21:00
00:00 to 23:50
21:00
21C Grid Usage End h:m
00:00 to 23:50
21:00
00:00 to 23:50
21:00
End Menu 21
22 Battery Xfer (BX) Menu
“22 Battery Xfer (BX) Menu” on page 7–18
for details.
22A High Xfer (HBX) Vdc
16.1 to 33.9
27.0
32.2 to 67.8
54.0
22B Low Xfer (LBX) Vdc
16.1 to 33.8
23.0
32.2 to 67.8
46.0
End Menu 22
23 ALM Relays Menu
“23 ALM Relays Menu” on page 7–19
for details.
23A RY9 VDC Energized
22.1 to 35.5
26.0
44.2 to 71.0
52.0
23B RY9 VDC DeEnergized
20.0 to 35.5
22.0
40.0 to 71.0
44.0
23C RY9 Delay at DeEngz.
Min
00 to 255
10
00 to 255
10
23D RY10 VDC Energized
10.0 to 32.0
28.8
20.0 to 64.0
57.6 Vdc
23E RY10 VDC DeEnergized 10.0 to 32.0
26.8
20.0 to 64.0
53.6 Vdc
23F RY10 Delay at DeEngz.
Min
00 to 255
10
00 to 255
10
23G RY11 Mode
Cooldown Error
Error
Cooldown Error Error
End Menu 23
24 Generator Timers Menu
“24 Generator Timers Menu” on page 7–26
for details.
24A Gen Run Time Start h:m 00:00 to 23:50
08:00
00:00 to 23:50
08:00