The following settings (
) are guidelines only. Refer to your
battery vendor for specific settings and battery maintenance guidelines.
Table 6-4 Battery Voltages For Setting Charging Parameters
Battery Type
BULK VOLTS
FLOAT VOLTS
Equalization Charge
Process
Set
Temp
Comp
24-volt
models
48-volt
models
24-volt
models
48-volt
models
Sealed Gel
Lead Acid
28.2 Vdc
56.4 Vdc
27.2 Vdc
54.4 Vdc
Not recommended -
consult manufacturer
LeadAcid
AGM
Lead Acid
28.8 Vdc
57.6 Vdc
26.8 Vdc
53.6 Vdc
Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations
LeadAcid
Maintenance-Free
RV/Marine
Lead Calcium
Battery
28.8 Vdc
57.6 Vdc
26.8 Vdc
53.6 Vdc
Not recommended -
consult manufacturer
LeadAcid
Deep-cycle,
Liquid Electrolyte
Lead Antimony
Battery
29.2 Vdc
58.4 Vdc
26.8 Vdc
53.6 Vdc
Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations
LeadAcid
NiCad or NiFe
Alkaline Battery
(using 10 cells in
series)
32.0 Vdc
64.0 Vdc
29.0 Vdc
58.0 Vdc
Consult Manufacturer
NiCad
Table 6-5 Battery Charging Current and Timer Default Settings
Menu Item
SW Plus
2524
Default
Settings
SW Plus
2548
Default
Setting
SW Plus
4024
Default
Settings
SW Plus
4048
Default
Setting
SW Plus
5548
Default
Setting
12E Max Charge Amps
20 amps
20 amps
30 amps
30 amps
40 amps
12F Bulk Done Amps AC
10 amps
10 amps
10 amps
10 amps
10 amps
12G EQ Vdc Done Timer h:m 02:00
02:00
02:00
02:00
02:00
12H Max Bulk/EQ Timer h:m 05:00
05:00
05:00
05:00
05:00
12I Temp Comp
LeadAcid
LeadAcid
LeadAcid
LeadAcid
LeadAcid