Xantrex Technology SW Plus 4024 User Manual
Page 151
![background image](/manuals/229206/151/background.png)
Basic Setup Summary
976-0043-01-02
6–3
11C Low Battery Cut Out Vdc
11.0 to 33.9
22.0
32.0 to 67.8
44.0
11D LBCO Delay Minutes
01 to 255
15
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
00 to 248
08
End Menu 11
12 Battery Charging Menu
“12 Battery Charging Menu” on page 6–19
for details.
12A Finish Stage
SILENT
FLOAT
FLOAT
SILENT
FLOAT
FLOAT
12B Bulk Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
12C Float Volts DC
20.0 to 32.0
26.8
40.0 to 64.0
53.6
12D Equalize Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
12E Max Charge Amps AC
01 to 20
20
01 to 20
20
12F Bulk Done Amps AC
00 to 20
10
00 to 20
10
12G EQ Vdc Done Timer
00:00 to 23:50 02:00
00:00 to
23:50
02:00
12H Max Bulk/EQ Timer
00:00 to 23:50 05:00
00:00 to
23:50
05:00
12I Temp Comp
LeadAcid
NiCad
LeadAcid
LeadAcid
NiCad
LeadAcid
End Menu 12
13 AC Inputs Menu
“13 AC Inputs Menu” on page 6–26
for details.
13A Grid (AC1) Amps AC
00 to 60
60
00 to 60
60
13B Gen (AC2) Amps AC
00 to 60
30
00 to 60
30
13C Input Upper Limit Vac
125 to 150
130
125 to 150
130
13D Input Lower Limit Vac
80 to 115
110
80 to 115
110
End Menu 13
14 Save/Restore Settings Menu
“14 Save/Restore Settings Menu” on page 6–29
for details.
14A Push INV now to save
settings
Push INV now to save settings
14B Push GEN to restore settings
Push GEN to restore settings
Table 6-1 Basic Setup Menu Default Settings for the Sine Wave Plus 2524 and 2548 Models
Basic Setup Menus
Sine Wave Plus
2524
Sine Wave Plus
2548
See Page
Range/
Display
Default
Range/
Display
Default