Table 6-2 – Xantrex Technology SW Plus 4024 User Manual
Page 152

Basic Setup Programming
6–4
976-0043-01-02
14C Push GEN for factory
defaults
Push GEN for factory defaults
End Menu 14
END BASIC SETUP MENU
Table 6-2 Basic Setup Menu Default Settings for the Sine Wave Plus 4024 and 4048 Models
Basic Setup Menus
Sine Wave Plus
4024
Sine Wave Plus
4048
See Page
Range/
Display
Default
Range/
Display
Default
10 Time of Day Setup Menu
“10 Time of Day Setup Menu” on page 6–11
for details.
10A Set Hour
00:00:00 to
23:50:00
00:00:00
00:00:00 to
23:50:00
00:00:00
10B Set Minute
00:00:00 to
00:09:00
00:00:00
00:00:00 to
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
00 to 59
00:00:00
End Menu 10
11 Inverter Setup Menu
“11 Inverter Setup Menu” on page 6–12
for details.
11A High Battery Cut Out Vdc
16.1 to 34.0
32.0
32.2 to 68.0
64.0
11B Low Battery Cut In Vdc
16.1 to 33.9
26.0
32.2 to 67.8
52.0
11C Low Battery Cut Out Vdc
11.0 to 33.9
22.0
32.0 to 67.8
44.0
11D LBCO Delay Minutes
01 to 255
15
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
00 to 248
08
End Menu 11
12 Battery Charging Menu
“12 Battery Charging Menu” on page 6–19
for details.
12A Finish Stage
SILENT
FLOAT
FLOAT
SILENT
FLOAT
FLOAT
12B Bulk Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
12C Float Volts DC
20.0 to 32.0
26.8
40.0 to 64.0
53.6
12D Equalize Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
Table 6-1 Basic Setup Menu Default Settings for the Sine Wave Plus 2524 and 2548 Models
Basic Setup Menus
Sine Wave Plus
2524
Sine Wave Plus
2548
See Page
Range/
Display
Default
Range/
Display
Default