Advanced Setup Menu
976-0043-01-02
B–11
24 Generator Timers Menu
“24 Generator Timers Menu” on page 7–26
for details.
24A Gen Run Time Start h:m
00:00 to
23:50
08:00
00:00 to
23:50
08:00
24B Gen Run Time Stop h:m
00:00 to
23:50
08:00
00:00 to
23:50
08:00
24C Quiet Time Begin h:m
00:00 to
23:50
08:00
00:00 to
23:50
08:00
24D Quiet Time End h:m
00:00 to
23:50
08:00
00:00 to
23:50
08:00
24E Gen Exercise Period Days
00 to 255
30
00 to 255
30
24F Gen Exercise Timer Min
00 to 255
15
00 to 255
15
24G Gen Cooldown Timer Min
00 to 255
02
00 to 255
02
24H RN2/Gen Run h:m
00:00 to
23:50
08:00
00:00 to
23:50
08:00
25 Gen Starting Details Menu
“25 Gen Starting Details Menu” on page 7–29
for details.
25A RY7 Mode
GS RN1 RN2 GS
GS RN1 RN2 GS
25B Gen Warmup
Second/Minute
0 to 127
/0 to 127
10 Seconds 0 to 127
/0 to 127
10 Seconds
25C Pre Crank Seconds
00 to 255
10
0 to 255
10
25D Max Crank Seconds
01 to 15
10
01to15
10
25E Post Crank Seconds
00 to 255
30
00 to 255
30
26 Gen Auto Run Setup Menu
“26 Gen Auto Run Setup Menu” on page 7–38
for details.
26A Load Start Amps AC
00 to 63
20
00 to 63
20
26B Load Start Delay Min
00.0 to 25.5
05.0
00.0 to 25.5
05.0
26C Load Stop Delay Min
00.0 to 25.5
05.0
00.0 to 25.5
05.0
26D 24-hr Start Volts DC
10.0 to 35.5
24.6
20.0 to 71.0
49.2
26E 2-hr Start Volts DC
10.0 to 35.5
23.6
20.0 to 71.0
47.2
26F 15-min Start Volts DC
10.0 to 35.5
22.6
20.0 to 71.0
45.2
Table B-5 Advanced Setup Default and User Settings for the Sine Wave Plus 2524 and
2548 Models
Advanced Setup Menus
Sine Wave Plus
2524
Sine Wave Plus
2548
User
Settings
Range/
Display
Default
Settings
Range/
Display
Default
Settings