Table 6-3 – Xantrex Technology SW Plus 4024 User Manual
Page 154
![background image](/manuals/229206/154/background.png)
Basic Setup Programming
6–6
976-0043-01-02
Table 6-3 Basic Setup Menu Default Settings for the Sine Wave Plus 5548 Model
Basic Setup Menus
Sine Wave Plus
5548
See Page
Range/
Display
Default
10 Time of Day Setup Menu
“10 Time of Day Setup Menu” on page 6–11
for details.
10A Set Hour
00:00:00 to
23:50:00
00:00:00
10B Set Minute
00:00:00 to
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
End Menu 10
11 Inverter Setup Menu
“11 Inverter Setup Menu” on page 6–12
for details.
11A High Battery Cut Out Vdc
32.2 to 68.0
64.0
11B Low Battery Cut In Vdc
32.2 to 67.8
52.0
11C Low Battery Cut Out Vdc
32.0 to 67.8
44.0
11D LBCO Delay Minutes
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
End Menu 11
12 Battery Charging Menu
“12 Battery Charging Menu” on page 6–19
for details.
12A Finish Stage
SILENT
FLOAT
FLOAT
12B Bulk Volts DC
40.0 to 64.0
57.6
12C Float Volts DC
40.0 to 64.0
53.6
12D Equalize Volts DC
40.0 to 64.0
57.6
12E Max Charge Amps AC
01 to 45
40
12F Bulk Done Amps AC
00 to 50
10
12G EQ Vdc Done Timer
00:00 to
23:50
02:00
12H Max Bulk/EQ Timer
00:00 to
23:50
05:00
12I Temp Comp
LeadAcid
NiCad
LeadAcid
End Menu 12