Advanced Setup Menu
976-0043-01-02
B–15
22B Low Xfer (LBX) Vdc
32.2 to 67.8
46.0
23 ALM Relays Menu
“23 ALM Relays Menu” on page 7–19
for details.
23A RY9 Vdc Energized
44.2 to 71.0
52.0
23B RY9 Vdc DeEnergized
40.0 to 71.0
44.0
23C RY9 Delay at DeEngz. Min
00 to 255
10
23D RY10 VDC Energized
20.0 to 64.0
57.6
23E RY10 VDC DeEnergized
20.0 to 64.0
53.6
23F RY10 Delay at DeEngz. Min
00 to 255
10
23G RY11 Mode
Cooldown
Error
Error
24 Generator Timers Menu
“24 Generator Timers Menu” on page 7–26
for details.
24A Gen Run Time Start h:m
00:00 to 23:50
08:00
24B Gen Run Time Stop h:m
00:00 to 23:50
08:00
24C Quiet Time Begin h:m
00:00 to 23:50
08:00
24D Quiet Time End h:m
00:00 to 23:50
08:00
24E Gen Exercise Period Days
00 to 255
30
24F Gen Exercise Timer Min
00 to 255
15
24G Gen Cooldown Timer Min
00 to 255
02
24H RN2/Gen Run h:m
00:00 to 23:50
08:00
25 Gen Starting Details Menu
“25 Gen Starting Details Menu” on page 7–29
for details.
25A RY7 Mode
GS RN1 RN2
GS
25B Gen Warmup
Second/Minute
0 to 127
/0 to 127
10 Seconds
25C Pre Crank Seconds
00 to 255
10
25D Max Crank Seconds
01 to 15
10
25E Post Crank Seconds
00 to 255
30
26 Gen Auto Run Setup Menu
“26 Gen Auto Run Setup Menu” on page 7–38
for details.
26A Load Start Amps AC
00 to 63
45
Table B-7 Advanced Setup Default and User Settings for the Sine Wave Plus 5548 Model
Advanced Setup Menus
Sine Wave Plus
5548
User Settings
Range/
Display
Default
Settings