Basic setup summary, Check defaults, Record changes – Xantrex Technology SW Plus 4024 User Manual
Page 150: Basic setup summary –2, Table 6-1

Basic Setup Programming
6–2
976-0043-01-02
Basic Setup Summary
Check Defaults
The following tables provides the default settings for the
Sine Wave Plus
Basic Setup Menu for each model and the cross-reference pages for
locating information on each menu item.
•
•
•
Table 6-3, “Basic Setup Menu Default Settings for the Sine Wave
Plus 5548 Model” on page 6–6
Record Changes
If your system requires changes to these default settings, record the
changes on the model-specific tables in
before your start programming. These tables are found on the
following pages:
•
•
•
Table B-4, “Basic Setup Default and User Settings for the Sine Wave
Plus 5548 Model” on page B–8
For directions on how to access the Basic Setup Menu, see
Basic Setup Menu” on page 6–10
.
Table 6-1 Basic Setup Menu Default Settings for the Sine Wave Plus 2524 and 2548 Models
Basic Setup Menus
Sine Wave Plus
2524
Sine Wave Plus
2548
See Page
Range/
Display
Default
Range/
Display
Default
10 Time of Day Setup Menu
“10 Time of Day Setup Menu” on page 6–11
for details.
10A Set Hour
00:00:00 to
23:50:00
00:00:00
00:00:00 to
23:50:00
00:00:00
10B Set Minute
00:00:00 to
00:09:00
00:00:00
00:00:00 to
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
00 to 59
00:00:00
End Menu 10
11 Inverter Setup Menu
“11 Inverter Setup Menu” on page 6–12
for details.
11A High Battery Cut Out Vdc
16.1 to 34.0
32.0
32.2 to 68.0
64.0
11B Low Battery Cut In Vdc
16.1 to 33.9
26.0
32.2 to 67.8
52.0