6F3B0253

Basic Hardware and Function

95

6. Programming Information

6.6.2

Sub-program #1

If the sub-program #1 is programmed, it is executed once at the beginning of the first
scan (before main program execution).

Therefore, the sub-program #1 can be used to set the initial value into the registers.
The sub-program #1 is called the initial program.

The figure below shows the first scan operation.

The end of the sub-program #1 is recognized by the END instruction.

6.6.3

Timer interrupt program

The timer interrupt is the highest priority task. It is executed cyclically with a user
specified interval, with suspending other operation.
The interrupt interval is set in the system information. (5 to 1000 ms, 5 ms units)

The end of the timer interrupt is recognized by the IRET instruction.

I/O

Main program

Main program

Sub#1

Timer

I/O

Mode

Timer

RUN mode

transition

1st scan

2nd scan

Time

1 scan

1 scan

1 scan

Scan

Timer interrupt

1 scan

Timer interrupt

interval

Timer interrupt

interval

Time