10. Troubleshooting

10.1.2 CPU check

If the PWR (power) LED is lit but the RUN LED is not lit, check the following points.

Check the position of the

If it is not in R (RUN) position, turn the

mode control switch

switch to R (RUN) position.

Check the FLT (fault) LED

If the FLT LED is lit or blinking, the T1-16S
is in the ERROR mode. Confirm the error

message by connecting the

programming

tool. Refer to section 10.2.

Is the RUN LED blinking ?

If it is blinking, the T1-16S is in the HOLD

mode. Check your program

whether the

HOLD device (S401) is

not used.

Connect the programming

If the T1-16S stays in HALT mode even

tool, and check the T1-16S’s

when the mode control switch is changed,

status

the switch may be faulty.
If the communication between the T1-16S
and the programming tool is not possible,
the T1-16S may be faulty.

10.1.3 Program check

Check the user program based on the following points if it is running but the operation
does not work as intended.

(1) Whether duplicated coils are not programmed.
(2) Whether a coil device and a destination of a function instruction are not

overlapping.

(3) Whether the ON/OFF duration of an external input signal is not shorter than the

T1-16S’s scan time.

(4) Whether a register/device, which is used in the main program, is not operated

erroneously in the interrupt program.

When you write/modify the program, it is necessary to execute the
EEPROM write operation before turning off power to the T1. Otherwise the
old program stored in the built-in EEPROM will be over-written, and your
program modification will disappear.

NOTE