1.8 Real-time data link system

TOSLINE-F10


TOSLINE-F10 is a high speed data transmission system suited for small points I/O
distribution system. By inserting the TOSLINE-F10 remote module (FR112M), the
T1-16S can work as a remote station of the TOSLINE-F10 network. On this network,
the T1-16S sends 1 word data to the master station and receives 1 word data from
the master station.

Item

TOSLINE-F10 system specifications

High speed mode

Long distance mode

Topology

Bus (terminated at both ends)

Transmission distance

(without repeater)

500 m max. (total)

1 km max. (total)

Transmission speed

750 kbps

250 kbps

Scan transmission
capacity

512 points (32 words) max.

Scan cycle

7 ms/32 words

12 ms/32 words

Error checking

CRC check





Typical data link configuration