Special i/o functions – Toshiba 6F3B0253 User Manual
Page 262

6F3B0253
260
T1-16S User’s Manual
8. Special I/O Functions
8.2 Variable input filter constant
Function
The input filter constant (ON/OFF delay time) of the leading 8 points X000 to X007
can be specified by user program within the range of 0 to 15ms. The default is 10ms.
The setting value is recognized at the first scan. Therefore, it cannot be changed after
the second scan.
Related registers
SW16
Function selection. Refer to section 8.1.
SW17
Input filter constant value
F E D C B A 9 8 7 6 5 4 3 2 1 0
No use (set to 0)
Setting value
0 to 15
Operation
Input signal
Internal logic
Scan cycle
X device
T: Input filter constant (0 to 15ms)
Sample program
This program sets the input filter constant to 3ms.
T
T
T
T