Instructions – Toshiba 6F3B0253 User Manual
Page 253

6F3B0253
Basic Hardware and Function
251
7. Instructions
< Read command mode (Mode 2) >
When the instruction input comes ON with the operand B+1 is 2, the Read command mode
(mode 2) is selected. In this mode, the T1-16S sends the user specified Read command to the
Inverter specified by the operand B, and repeats.
Sends the specified command to #n Inverter
Receives the response and stores the data into the register
The target Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command setting register and the response data storing register is indirectly specified by
the operand A and A+1.
When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter.
Example
Data table designation
Parameter & status
RS-485 port
D1000
4
RW200
3
D1010
H0030 (fixed)
D1001
3000
RW201
2 (mode 2)
D1011
0 (fixed)
RW202
Execution status
RW203
Comm error code
RW204
RW205
Inverter comms
RW206
status map
RW207
When the data for each operand are set as above, the following operation condition is specified.
•
RW200=3
⇒
The target Inverter number is 3. Therefore T1-16S communicates with #3 Inverter.
•
D1000=4 & D1001=3000
⇒
D3000 is specified as the command setting register and D3001 is specified
as the response data storing register.
Data table:
Register
Data contents
Signal direction
D3000
Command code
D3001
Response data
←
Read
Example operation:
For example, to read the output current from the #3 Inverter, set the command code HFE03 into
D3000. Then the response data is stored in D3001. If the response data is 1915, it means 19.15 %.
For the command code and the data format of the response, refer to your Inverter manual.
Repeat