7. Instructions
FUN 146
STOT
Step sequence output
Expression
Input
−
[ STOT A ]
−
Function
When the input is ON, the device A is set to ON and the devices of STIN instructions on the same
rung are reset to OFF.
Execution condition
Input
Operation
Output
OFF
No execution
-
ON
Execution
-
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW T
C
D
I
J
K
A Step device
√
Example
See example on STIN (FUN 145) instruction.
Note
•
The STIZ, STIN and STOT instructions are used together to configure the step sequence.
•
Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.
•
Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop
or convergence of sequences. (Max. 11 STIN instructions on one rung)
•
To perform the conditional branch (sequence selection), separate the rungs as follows.
This limitation is applied to T1 version 1.00 only.
[ STIN A ]
| |
[ STOT B ]
[ STIN A ]
| |
[ STOT B ]
| |
[ STOT C ]
[ STIN A ]
| |
[ STOT C ]
Not allowed
Available