beautypg.com

Programming information – Toshiba 6F3B0253 User Manual

Page 102

background image

6F3B0253

100

T1-16S User’s Manual

6. Programming Information

6.9 On-line debug support functions

The following on-line (during RUN) functions are supported in the T1-16S for effective
program debugging.

On-line function

4 k mode

8 k mode

Force function

Yes

Yes

Sampling trace function

Yes

Yes

Changing timer /counter
preset value

Yes

Yes

Changing constant operand of
function instruction

Yes

Yes

Changing device directly

Yes

Yes

Program changing in edit
mode

Yes

No

EEPROM write command

Yes

Yes

Refer to section 6.5 for 4 k/8 k mode.

Force function

Two types of force functions are available, input force and coil force.
The input force is used to disable the external input signals. When an external input
device is designated as forced input, the ON/OFF state of the device can be changed
manually by using the data setting function of the programming tool, regardless of the
corresponding external signal state. The input force designation is available for the
external input devices (X).
The coil force is used to disable the coil instruction. When a coil instruction on the
program is designated as forced coil, the ON/OFF state of the coil device can be
changed manually by using the data setting function of the programming tool,
regardless of the coil circuit execution status.
On the programming tool, the forced input and forced coil are expressed as follows.

Forced input

Forced

Normal

X005

x005

Forced coil

Forced

Normal

Y023

Y023

If EEPROM write operation is executed with remaining the force
designation, the force designation is also saved into the built-in EEPROM.
Because the force function is debugging function, release all force
designation before executing the EEPROM write operation. The force batch
release command is available when the T1-16S is in HALT mode.

NOTE

NOTE