4. Installation and Wiring
4.1 Environmental conditions
Do not install the T1-16S in the following locations:
•
Where the ambient temperature drops below 0
°
C or exceeds 55
°
C.
•
Where the relative humidity drops below 20% or exceeds 90%.
•
Where there is condensation due to sudden temperature changes.
•
In locations subject to vibration that exceeds tolerance.
•
In locations subject to shock that exceeds tolerance.
•
Where there are corrosive or flammable gases.
•
In locations subject to dust, machining debris or other particles.
•
In locations exposed to direct sunlight.
Observe the following precautions when installing enclosures in which the T1-16S will
be installed:
•
Provide the maximum possible distance from high-voltage or high-power panels.
This distance must be at least 200mm.
•
If installing the enclosures in the vicinity of high-frequency equipment, be sure to
correctly ground the enclosures.
•
When sharing the channel base with other panels, check for leakage current from
the other panels or equipment.
!
CAUTION
Excess temperature, humidity, vibration, shocks, or dusty and corrosive
gas environment can cause electrical shock, fire or malfunction.
Install and use the T1-16S and related equipment in the environment
described in this section.