4. Installation and Wiring
4.5 Power supply wiring
Wire the power source to the T1-16S power supply terminals.
Insulation
transformer
Line filter
Power source
T1-16S
•
Power
conditions:
AC power supply type
DC power supply type
Rated voltage
100 to 240Vac, +10/-15%
24Vdc, +20/-15%
Frequency
50/60Hz,
±
5%
-
Power consumption
45VA or less
18W or less
Retentive power
interruption
Continuous operation for less than 10ms
•
1.25mm
2
(16 AWG) twisted-pair cable should be used for the power cable.
•
The power cable should be separated from other cables.
!
CAUTION
1. Turn off power before wiring to minimize the risk of electrical shock.
2. Applying excess power voltage to the T1-16S can cause explosion or
fire. Apply power of the specified ratings described below.