beautypg.com

Instructions – Toshiba 6F3B0253 User Manual

Page 249

background image

6F3B0253

Basic Hardware and Function

247

7. Instructions

< Data exchange mode (Mode 0) >

When the instruction input comes ON with the operand B+1 is 0, the Data exchange mode
(mode 0) is selected. In this mode, the T1-16S sends the following commands to the Inverters
starting from #0 through the Inverter number specified by the operand B, and repeats.

#0

Frequency reference write (FA01)

#0

Operation command write (FA00)

#1

Frequency reference write (FA01)

#1

Operation command write (FA00)

:
#n

Frequency reference write (FA01)

#n

Operation command write (FA00)

#0

Operating frequency monitor (FD00)

#0

Output terminal status monitor (FE07)

#1

Operating frequency monitor (FD00)

#1

Output terminal status monitor (FE07)

:
#n

Operating frequency monitor (FD00)

#n

Output terminal status monitor (FE07)

The maximum Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command data table is specified by the operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter currently communicating.

Example

Data table designation

Parameter & status

RS-485 port

D1000

4

RW200

5

D1010

H0030 (fixed)

D1001

2000

RW201

0 (mode 0)

D1011

0 (fixed)

RW202

Execution status

RW203

Comm error code

RW204
RW205

Inverter comms

RW206

status map

RW207

When the data for each operand are set as above, the following operation condition is specified.

RW200=5

The max Inverter number is 5. Therefore T1-16S scans from #0 through #5 Inverters.

D1000=4 & D1001=2000

D2000 is specified as the data table starting address.

Scan