7. Instructions

CNT

Counter

Expression

Count input

C

CNT

Q

Output

Enable input

E

A B

Function

While the enable input is ON, this instruction counts the number of the count input changes from
OFF to ON. The count value is stored in the counter register B. When the count value reaches the
set value A, the output and the counter device corresponding to B are turned ON. When the enable
input comes OFF, B is cleared to 0 and the output and the counter device are turned OFF.
The available data range for operand A is 0 to 65535.

Execution condition

Enable

input

Operation

Output

OFF

No operation (B is cleared to 0)

OFF

ON

Count value (B)

<

set value (A)

OFF

Count value (B)

set value (A)

ON

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Set value

0 - 65535

B Count value

Example

X001

X002

C010

C.010

Y021

Note

No transitional contact is required for the

count input. The count input rising edge is
detected by this instruction.

For the count input, direct linking to a

connecting point is not allowed. In this
case, insert a dummy contact (always ON
= S04F, etc.) just before the input.
Refer to Note of Shift register FUN 074.