beautypg.com

I/o application precautions, Warning – Toshiba 6F3B0253 User Manual

Page 50

background image

6F3B0253

48

T1-16S User’s Manual

3. I/O Application Precautions

3.1 Application precautions for input signals

(1) Minimum ON/OFF time of the input signal

The following conditions guarantee correct reading of the ON/OFF state of the input
signal:
Input ON time: ON delay time + the time for one scan
Input OFF time: OFF delay time + the time for one scan
The ON and OFF times of the input signals must be longer than these intervals.

(2) Increasing the contact current

The reliability of some contacts cannot be guaranteed by the specified input current. In
this case, install an external bleeder resistor to increase the contact current.

T1
input
circuit

I

1

I

Bleeder resistor

R

V

I

2

R

V

I

I

Wattage

V

R

=

>

×

1

2

3

(3) Connecting transistor output device

An example of connecting a transistor output device to T1-16S’s input circuit is shown
below.

For NPN open collector

For PNP open collector

C

T1
input
circuit

T1
input
circuit

C

!

WARNING

Configure emergency stop and safety interlocking circuits outside the
T1-16S. Otherwise, malfunction of the T1-16S can cause injury or serious
accidents.