beautypg.com

Toshiba 6F3B0253 User Manual

Page 18

background image

6F3B0253

16

T1-16S User’s Manual

1. System Configuration

1.2 Features

I/O module support:
The T1-16S has an interface for connecting the I/O modules. Up to eight modules
can be connected to the T1-16S.
By using the 16 points I/O module, the T1-16S can control up to 144 I/O points.

Built-in high-speed counter:
Two single-phase or one quadrature (2-phase) pulses can be counted. The
acceptable pulse rate is up to 5 kHz. (DC input type only)

Built-in analog setting adjusters:
Two analog setting adjusters are provided on the T1-16S. This allows operators to
adjust time or other control parameters easily using a screwdriver.

High speed processing:
Sophisticated machine control applications require high speed data manipulations.
The T1-16S is designed to meet these requirements.

1.4

µ

s per contact

2.3

µ

s per coil

4.2

µ

s per 16-bit transfer

6.5

µ

s per 16-bit addition

The T1-16S also supports interrupt input function (DC input type only). This allows
immediate operation independent of program scan.

High performance software:
The T1-16S offers 21 basic ladder instructions and 97 function instructions.
Subroutines, Interrupt functions, Indirect addressing, For/Next loops, Pre-derivative
real PID, etc. are standard on the T1-16S. These functions allow the T1-16S to be
applied to the most demanding control applications.

Battery-less operation:
The T1-16S has a standard built-in EEPROM, permitting operation without need of a
battery. Also, the variable data can be written into and/or read from the EEPROM,
providing completely maintenance-free back-up operation.
This function is an important feature for OEMs, because it can eliminate the need for
changing the battery every few years.
(Optional battery is also available to back-up real-time clock and retentive data)