beautypg.com

Instructions fun 149 u/d up-down counter – Toshiba 6F3B0253 User Manual

Page 218

background image

6F3B0253

216

T1-16S User’s Manual

7. Instructions

FUN 149

U/D

Up-down counter

Expression

Direction input

U

U/D

Q

Output

Count input

C

Enable input

E

A

Function

While the enable input is ON, this instruction counts the number of the count input changes from
OFF to ON. The count direction (up count or down count) is selected by the state of the direction
input. The count value is stored in the counter register A. The count value range is 0 to 65535.

Up count when the direction input is ON

Down count when the direction input is OFF

When the enable input is OFF, the counter register A is cleared to 0.

Execution condition

Enable

input

Operation

Output

OFF

No operation (A is cleared to 0)

OFF

ON

Count value is not limit value (0 or 65535)

OFF

Count value is limit value and count input is ON

ON

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Count value

Example

X005

X006

R010

C005

C.005

Note

The transitional contact is required for

the count input. Otherwise, counting is
executed every scan during X005 is ON
in this example.

For the direction input and the count

input, direct linking to a connecting point
is not allowed. Refer to Note of Shift
register FUN 074.

2 3

3

2

2

1

1

1