Instructions fun 144 stiz step sequence initialize – Toshiba 6F3B0253 User Manual
Page 214

6F3B0253
212
T1-16S User’s Manual
7. Instructions
FUN 144
STIZ
Step sequence initialize
Expression
Input
−
[ STIZ (n) A ]
−
Output
Function
When the input is ON, n devices starting with A are reset to OFF, and A is set to ON.
This instruction is used to initialize a series of step sequence. The step sequence is useful to
describe a sequential operation.
Execution condition
Input
Operation
Output
OFF
No execution
OFF
ON
Execution at the rising edge of the input
ON
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW T
C
D
I
J
K
n Size of step
sequence
1 - 64
A Start device
√
Example
When R020 is changed from OFF to ON, R400 is set to ON and subsequent 9 devices (R401
to R409) are reset to OFF.
This instruction initializes a series of step sequence, 10 devices starting with R400.
R409
R408
R407
R406
R405
R404
R403
R402
R401
R400
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
10 devices starting with R400
Note
•
The STIZ instruction is used together with STIN (FUN 145) and STOT (FUN 146) instructions to
configure the step sequence.
•
The STIZ instruction is executed only when the input is changed from OFF to ON.